Waveware comPPage DVIF-10 Manual de usuario Pagina 11

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 14
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 10
Alarm Interface Utility Software V3.1.3
Specifications
Input Voltage 12 Volts DC
Current 750 mA maximum, Normal – 425mA
Input Contacts 10 per unit, Maximum 40
Input Selection No jumper Voltage
Jumper Dry
Fused Inputs – 125 Volts DC / 450mA
Input No Voltage (dry)
Voltage – AC or DC 1-24 Volts
Inputs can be Mixed
Connection RJ45 Cable using RS485 Total 4 Units
Protocol Scope and Motorola Comp2
Programming PC software via RS232 9 pin connector
Repeat Message 0-4 or Change of State, with intervals of 1-59
minutes
Message Open state and Closed state
Message Length Each message has a maximum length of 80
characters
Pager Cap Code Each Contact has Individual Pager ID
Message Alert Type A,B,C or D selectable for each Contact
Approval FCC Part 15, RoHS Compliant
Size 7.10 in x 3.52 in x 1.17 in
Warranty Life
RS232 Cable Pin Out
Null Modem (Special)
9-Pin F/F
1-nc, 2-3,3-2,4-6,6-4,5-5,7-8,8-7, 9-9
Serial Straight Through
9-Pin M/F
1-1,2-2,3-3,4-4,5-5,6-6,7-7,8-8, 9-nc