1. From the Setup menu select Board and from the sub-menu that appears select Opto Input Type.
The following Window is displayed.
2. Select either Normally Open or Normally Closed. This selection should match the output type
of the normal contact condition on the host system. A change from the selected normal input
condition initiates the “ON” message to the pager. Click OK.
Opto Input Message Setup
1. From the Setup menu select Board and from the sub-menu that appears select Paging Messages.
The following Window will appear.
2. Select the Input Point number to be programmed by clicking on the corresponding Input Select
Button.
3. Click the cursor in the Pager ID box and enter the pager number that messages for this input are
to be sent to.